Active reactive and impedance. Resistance triangles


Star and triangle connection principle. Features and operation

To increase the transmission power without increasing the network voltage, to reduce voltage ripple in power supplies, to reduce the number of wires when connecting the load to the power supply, various circuits for connecting the windings of power sources and consumers (star and delta) are used.

Scheme

The windings of generators and receivers when working with 3-phase networks can be connected using two circuits: star and triangle. Such circuits have several differences among themselves; they also differ in current load. Therefore, before connecting electrical machines, it is necessary to find out the difference in these two circuits - star and triangle.

Star diagram

Connecting different windings according to a star circuit involves connecting them at one point, which is called zero (neutral), and is designated on the diagrams “O”, or x, y, z. The neutral point may have a connection to the power supply neutral point, but not all cases have such a connection. If there is such a connection, then such a system is considered 4-wire, and if there is no such connection, then it is considered 3-wire.

Triangle diagram

With this scheme, the ends of the windings are not combined into one point, but are connected to another winding. That is, the result is a circuit similar in appearance to a triangle, and the windings in it are connected in series with each other. It should be noted that the difference from the star circuit is that in the delta circuit the system is only 3-wire, since there is no common point.

In a triangle circuit, when the load is off and the EMF is symmetrical, it is 0.

Phase and linear quantities

In 3-phase power networks there are two types of current and voltage - phase and linear. Phase voltage is its value between the end and beginning of the receiver phase. Phase current flows in one phase of the receiver.

When using a star circuit, the phase voltages are Ua, Ub, Uc , and the phase currents are I a, I b, I c . When using a delta circuit for load or generator windings, phase voltages are Uaв, Ubс, Uca , phase currents are I ac, I bс, I са .

Linear voltage values ​​are measured between the beginnings of phases or between linear conductors. Line current flows in the conductors between the power source and the load.

In the case of a star circuit, linear currents are equal to phase currents, and linear voltages are equal to U ab, Ubc, U ca. In a triangle circuit, everything turns out the other way around - phase and linear voltages are equal, and linear currents are equal to I a, I b, I c .

Great importance is given to the direction of the EMF of voltages and currents in the analysis and calculation of 3-phase circuits, since its direction affects the relationship between the vectors on the diagram.

Features of the circuits

There is a significant difference between these schemes. Let's figure out why different circuits are used in different electrical installations, and what their features are.

When starting an electric motor, the starting current has an increased value, which is several times greater than its rated value. If this is a low-power mechanism, then the protection may not work. When a powerful electric motor is turned on, the protection will definitely work, turning off the power, which will cause a voltage drop for some time and blown fuses, or turn off the electrical circuit breakers. The electric motor will operate at a low speed, which is less than the rated speed.

It can be seen that there are many problems arising due to the high inrush current. It is necessary to somehow reduce its value.

To do this, you can use some methods:
  • Connect a rheostat, inductor, or transformer to start the electric motor.
  • Change the type of connection of the electric motor rotor windings.

In industry, the second method is mainly used, since it is the simplest and gives high efficiency. The principle of switching the windings of an electric motor to circuits such as star and triangle works here. That is, when the motor is started, its windings have a “star” connection, after a set of operating speeds, the connection diagram changes to “triangle”. They have learned to automate this switching process in industrial settings.

In electric motors, it is advisable to use two circuits at once - star and triangle. It is necessary to connect the neutral of the power source to the zero point, since when using such circuits there is an increased likelihood of phase amplitude distortion. The source neutral compensates for this asymmetry, which arises due to different inductive resistances of the stator windings.

Advantages of the schemes
Star connection has important advantages:
  • Smooth start of the electric motor.
  • Allows the electric motor to operate with the declared rated power corresponding to the passport.
  • The electric motor will have a normal operating mode in various situations: with high short-term overloads, with long-term minor overloads.
  • During operation, the motor housing will not overheat.

The main advantage of the triangle circuit is to obtain the highest possible operating power from the electric motor. It is advisable to maintain operating modes according to the engine passport. When studying electric motors with a triangle circuit, it turned out that its power increases 3 times compared to a star circuit.

When considering generators, the star and delta circuits are similar in parameters to the operation of electric motors. The output voltage of the generator will be higher in a delta circuit than in a star circuit. However, as the voltage increases, the current decreases, since according to Ohm's law these parameters are inversely proportional to each other.

Therefore, we can conclude that with different connections of the ends of the generator windings, two different voltage ratings can be obtained. In modern powerful electric motors, when starting the circuit, star and delta switch automatically, as this makes it possible to reduce the current load that occurs when starting the motor.

In vector diagrams, a right triangle of voltages can be distinguished.

Taking into account the dependence of the xL

and
xC,
three circuit operating modes are possible:

a) the circuit voltage leads the current in phase by an angle j and the circuit as a whole has an active-inductive character;

b) the circuit voltage lags in phase with the current by an angle j and the circuit as a whole has an active-capacitive character;

c) voltage and current are in phase, the nature of the circuit as a whole is purely active. This circuit mode is usually called voltage resonance

, at which UL=UC,
xL
=
xC
.
You can tune the circuit to voltage resonance by changing xL
or
xC,
ᴛ.ᴇ.
changing C, L or f
(the frequency at which resonance occurs
f = 1/(2π√LC)).
At voltage resonance, the circuit resistance is minimal and the current is maximum.

Power supply circuits in the construction industry most often have an active-inductive nature; therefore, we will further consider the corresponding triangles with a positive angle j.

Using the Pythagorean theorem, it is possible to establish a connection between the complete

voltage of the circuit and voltages in its individual sections:

.

If we divide the sides of the voltage triangle by current (in a circuit with a series connection of elements, the current is the same in all sections), then (in accordance with Ohm’s law) we obtain a resistance triangle.

Here x=xL - xC

is the reactance of the circuit, and
Z
is
the total
resistance of the circuit:

.

The resulting equation establishes the relationship between various circuit resistances.

If we multiply the sides of the voltage triangle by the current, we get a power triangle:

Here P=URI

-
active power , which is released at the active resistances of the circuit. It is associated with irreversible transformations of electrical energy, that is, with the performance of work (useful) in an electrical installation. Active power is measured in watts
[W].

Q=UxI


reactive power. In electrical installations it is associated with reversible energy transformations; it does not perform useful work. In electrical installations it is spent on creating electric ( C
) and magnetic (
L
) fields.
Reactive power is measured in reactive volt amperes
[var].

Reactive power has a significant impact on the operating mode of an electrical circuit. Circulating through the wires of transformers, generators, engines, power lines, it heats them. For this reason, the calculation of wires and other elements of alternating current devices is made from total power , which takes into account active and reactive power.

S=UI - total power , measured in volt amperes

[B*A]. From the power triangle we determine:

.

Connecting energy receivers in a triangle

When connecting energy receivers with a triangle (Fig. 6-11), each phase of the receiver is connected to the linear wires, i.e., it is switched on to the line voltage, which will also be the phase voltage of the receiver:

Thus, changing the phase resistance does not affect the phase voltages.

We will take the directions of linear currents from the generator to the receiver as positive (Fig. 6-11). Directions of phase currents from A'

to
B',
from
B'
to
C
' and from
C'
to
A'
will also be taken as positive.

According to Kirchhoff's first rule for instantaneous current values ​​for node A'

you can write:

Similarly for node B':

Rice. 6-11

. Connecting receivers in a triangle

Consequently, the instantaneous value of any line current is equal to the algebraic difference of the instantaneous values ​​of the currents of those phases that are connected to a given wire.

Rice. 6-12.

Vector diagram when connecting receivers in a triangle.

The vector of any line current is found as the difference between the vectors of the corresponding phase currents:

In Fig. 6-12 shows a vector diagram for a three-phase circuit when connecting energy receivers with a triangle. In this diagram, all vectors are drawn from the same origin. In Fig. 6-13 shows a second diagram for the same circuit, on which the voltage vectors form a triangle, and the vector of each phase current is drawn from the same origin with the vector of the corresponding phase voltage.

Rice. 6-13.

Vector diagram when connecting receivers in a triangle.

If, with a symmetrical system of linear voltages, the phase load is uniform, i.e.

then the effective values ​​of the phase currents are equal to each other and they are shifted in phase by equal angles from the corresponding voltages (Fig. 6-14) and, therefore, by angles of 120° relative to each other. Therefore, the phase currents represent a symmetrical system. Linear currents will also represent a symmetrical system (Fig. 6-14).

By restoring the perpendicular from the middle of the linear current vector, for example IA,

we obtain a right triangle
OHM,
from which it follows that

Thus, when connecting receivers in a triangle with a uniform phase load, the linear currents are √3 times greater than the phase currents.

In addition, from the same vector diagram it follows that linear currents lag behind the corresponding phase currents at angles of 30°.

Rice. 6-14.

Vector diagram for a circuit connected by a triangle with a uniform phase load.

When connecting receivers in a triangle with a uniform phase load, the calculation of a three-phase circuit is reduced to the calculation of one phase.

in phase voltage are determined from the expressions

Active power of one phase

Three phase reactive power

Three-phase apparent power

If the phase load is uneven, the power of a three-phase circuit is determined as the sum of the powers of the individual phases.

If the energy receivers are connected by a star and the positive direction of the linear currents is taken to be the direction from the generator to the consumer, then according to Kirchhoff’s first rule for the neutral point we can write:

If the energy receivers are connected by a triangle, then the sum of the line currents

Consequently, for any method of connecting receivers, the algebraic sum of the instantaneous values ​​of the linear currents of a three-phase three-wire circuit is equal to zero.

Therefore, for example, the magnetizing force of the three cores of a three-phase cable is zero and, therefore, there is no magnetization of the steel armor of the cable used to protect against mechanical damage.

Voltage triangle, apparent power

In the electrical circuit shown in Fig. 2.6, elements r ,
L
and
C
are connected in series and connected to a sinusoidal voltage source. The current in this circuit varies according to a sinusoidal law.

Rice. 2.6. Electrical circuit diagram with r ,
L , C
elements

The equation of the electrical state of the circuit for instantaneous voltage values ​​has the form

.

The equation of electrical state can be written in the same way as the sum of voltage vectors, i.e. the voltage vector at the input of the circuit is equal to the sum of the voltage vectors on elements r ,
L
and
C
:

Comparing the right-hand sides of the equations of electrical state, written for instantaneous values ​​and in the form of vectors, it is clear that the voltage Ur

on element
r
is in phase with the current, voltage
UL
on element
L
leads the current by an angle , voltage
UC
on element
C
lags the current by an angle .
A sum-of-vectors equation can be represented as a geometric sum of vectors in a vector diagram. The construction of a vector diagram begins with the current vector, since when r , L
and
C
, it is common to all elements in the circuit (Fig. 2.7).

Rice. 2.7. Vector diagram for r ,
L , C
circuit

Let's direct the current vector along the horizontal axis (see Fig. 2.7). Voltage vectors in sections are constructed based on the conditions of bypassing the circuit against the direction of the current. The voltage vectors are directed towards increasing potential.

The potential of point 0 is equal to zero, the vector coincides with the current vector and is directed away from the point 0

to point
c.
The voltage on the element
L
leads the current by an angle , the vector is constructed from point
c
to point
b
at an angle to the current vector (see Fig. 2.7).
The voltage on element C
lags behind the current by an angle , therefore, the vector must be directed in the direction of the lag, i.e.
on the diagram from point b
down to point a
( U C < UL ).
By connecting the origin of coordinates with the end of the vector
U C
, we obtain the source voltage vector
Ua 0
. Vectors and form a right triangle of stresses.

From the stress triangle we find:

.

Dividing the voltage by the current gives the expression for the total resistance:

,

(2.25)

where is the reactance of the electrical circuit.

In the vector diagram, this expression corresponds to a resistance triangle, the sides of which are in I

times the reduced sides of the stress triangle (Fig. 2.8).

Rice. 2.8. Triangle of resistances

From the resistance triangle you can determine the phase angle φ

between current and voltage:
.
In electrical engineering it is customary to denote the angle φ

an arrow directed from the current vector to the voltage vector.
The sign of the angle φ
in the expression for the instantaneous value of current
i
is determined by the nature of the load: with the inductive nature of the load (
xL > x C
), the current lags behind the voltage by an angle
φ
, and in the expression for the instantaneous current, the angle
φ
is written with a minus sign: ;
when the load is capacitive ( xL < x C
), the current leads the voltage, and the angle
φ
is written with a plus sign: .

Instantaneous power rL C

the circuit can be represented as follows:

.

(2.26)

Having chosen the zero initial phase of the current, we obtain the following expressions for voltages

After substituting voltages and currents into expression (2.26), we determine the instantaneous power of the circuit: .

Components pL

and
pC
of instantaneous power change with double frequency and at each moment of time have opposite signs. Average or active circuit power

.

(2.27)

Active power is always positive.

Reactive power, which determines the exchange of energy between the circuit and the power source, is found from the formula

.

(2.28)

Reactive power can be positive when the load is inductive ( xL >
x C
) or negative when the load is capacitive (
xL < xC
).

The total power of the circuit is determined by the formula

.

(2.29)

Active, reactive and apparent power, as well as voltage and resistance, form a power triangle (Fig. 2.9).

The sides of the power triangle are in I

times the sides of the stress triangle are enlarged.

Rice. 2.9. Capacity Triangle

  • Back
  • Forward

INCLUSION OF ENERGY RECEIVERS INTO THE THREE-PHASE CURRENT NETWORK

Electric lamps are manufactured for rated voltages of 127 and 220 V, and three-phase electric motors for rated phase voltages of 127, 220 and 380 V

and higher.

The method of connecting the receiver to a three-phase current network depends on the line voltage of the network and on the rated voltage of the receiver.

Lamps with a nominal voltage of 127 V

switched on by a triangle at a linear network voltage of 127
V
and a star with a neutral wire at a linear network voltage of 220
V.
Lamps with a rated voltage of 220
V
are connected by a triangle into a network with a linear voltage of 220
V
and a star with a neutral wire into a network with a linear voltage of 380
V.
A three-phase electric motor is connected by a delta into a network whose line voltage is equal to the rated phase voltage of the electric motor. If the line voltage of the network exceeds √3 times the rated phase voltage of the electric motor, then it is turned on as a star.

Article on the topic Connecting energy receivers with a triangle

Star connection of transformer windings

When connected into a star, the following relations apply:

  • line currents are equal to phase currents,
  • linear voltages are √3 times greater than phase voltages

There are many options for connecting the transformer windings in a star, some of them are shown in the figure below. And, as they say, not all of them are equally useful, or rather, different connection diagrams are needed for different cases.

It should be noted that either one three-phase transformer or three single-phase ones can be connected into a star. The figure indicates:

  • A, B, C – the beginning of the high voltage windings
  • X, Y, Z – ends of high voltage windings
  • a, b, c – the beginning of the low voltage windings
  • x, y, z – ends of low voltage windings

Connection of transformer windings in a triangle

The triangle connection is so called because of its external resemblance to a triangle (seen in the figure).

When connected into a triangle, the following relations apply:

  • linear currents are √3 times greater than phase currents
  • line voltages are equal to phase voltages

The three secondary windings, when connected in a delta, are connected in series, thereby forming a closed circuit. There is no current in this circuit, since the EMF of the phases are shifted by 120 degrees and their sum at each moment of time is zero. Also, the current is zero if the following conditions are met: the EMF has a sinusoidal shape, the windings have the same number of turns.

Star and triangle in the question of third harmonics of transformers

In transformers, the triangle circuit is used, among other things, to obtain third harmonic currents, which are necessary to create a sinusoidal EMF of the secondary windings. In other words, to eliminate the third harmonic component in the magnetic flux.

To introduce third harmonics when connecting to a star, the neutral of the star is connected to the neutral of the generator, and the third harmonics begin to run along this path.

Connecting transformer windings in a zigzag

A zigzag connection is used when there is uneven load on the secondary loads. After the zigzag connection, the load is distributed more evenly across the phases and the magnetic flux of the transformer remains in balance despite the uneven load.

Consider the zigzag star connection of a three-phase power transformer. A schematic representation is shown in the figure.

The primary windings are connected in a star. Next, we divide each secondary winding in half. And then we connect as shown in the figure.

When connecting into a zigzag star, a larger number of turns will be required than with a simple star. Also, with this connection it is possible to obtain three voltage classes, for example 380-220-127V.

Bookmark or share with friends

Source: pomegerim.ru

§ 79. Triangle connection

In addition to a star connection, generators, transformers, motors and other three-phase current consumers can be connected in a delta.

In Fig. 179 shows an uncoupled three-phase system. By combining the wires of an unconnected six-wire system in pairs and connecting the phases as indicated in the drawing, we move on to a three-phase three-wire system connected by a triangle.

Rice. 179. Uncoupled three-phase system

As can be seen from Fig. 180, the delta connection is made so that the end of phase A is connected to the beginning of phase B, the end of phase B is connected to the beginning of phase C, and the end of phase C is connected to the beginning of phase A. Line wires are connected to the phase connections.

Rice. 180. Connected three-phase delta-connected system

If the generator windings are connected by a triangle, then, as can be seen in Fig. 180, line voltage is created by each phase winding. For a delta-connected consumer, the line voltage is connected to the phase resistance terminals. Therefore, when connected by a triangle, the phase voltage is equal to the linear voltage:

Let us determine the relationship between phase and linear currents when connected by a triangle, if the load of the phases is the same in size and nature. We compose the current equations according to Kirchhoff’s first law for three nodal points A 1, B 1 and C 1 of the consumer:

From this it can be seen that the linear currents are equal to the geometric difference of the phase currents. With a symmetrical load, the phase currents are equal in magnitude and shifted one relative to the other by 120°. By subtracting the phase current vectors according to the resulting equations, we obtain linear currents (Fig. 181). The relationship between phase and line currents when connected in a triangle is shown in Fig. 182:

Rice. 181. Phase and line currents when connected by a triangle

Rice. 182. Dependence between phase and linear currents when connected by a triangle

Therefore, with a symmetrical delta-connected load, the line current is √3 times the phase current.

In Fig. 183 shows a vector diagram of currents and voltages for a uniform active-inductive load connected by a triangle. The diagram is constructed as follows. On the selected scale, we build an equilateral triangle of linear network voltages UAB, UBC AND UAC, which are equal to the phase voltages of the consumer. In the direction of the lag at angles φAB, φBC, φCA to the linear voltages UAB, U BC and UCA, we plot the phase current vectors IAB, IBC and ICA on a scale. Then, as stated earlier, we determine the line currents IA, IB and IC.

Rice. 183. Vector diagram of currents and voltages with a uniform load connected by a triangle

For motors and other consumers of three-phase current, in most cases, all six ends of the three windings are brought out, which, if desired, can be connected either by a star or a triangle. Usually a board made of insulating material (terminal board) is attached to a three-phase machine, to which all six ends are brought out.

Triangles of conductivities and powers

Current triangles

Design relationships in parallel

RLC circuits. Triangles of currents and conductivities

In the vector diagrams for the first two modes, current triangles

,
allowing you to write down the calculated relationships for the effective or amplitude values ​​of all current components.
Such a triangle of currents for the active-inductive mode of the operating circuit is shown in Fig. 4.8, a, and for the active-capacitive mode in Fig. 4.8, b. Figure 4.8 - Current triangles

From the triangles it follows that any sinusoidal current can be decomposed into active and reactive components:

the active component of the current is in phase with the voltage and is equal to the projection of the current onto the direction of the voltage;

the reactive component of the current is phase shifted relative to the voltage by an angle π/2.

From the current triangles follows a number of calculation formulas for parallel RLC

-chains:

I ==; (4.21)

φ = arcsin

=
arccos
=
arctg
.

From the current triangle (Fig. 4.8) you can move to a new triangle if you divide the lengths of its sides by the effective value of the voltage at the circuit terminals U

(as shown in Fig. 4.9,a) and introduce, taking into account formulas (4.3), (4.4), the notation:

= g

;
= bL
;
= bC
;
= b
;
= y
, (4.22)

Date added: 2013-12-14; ; Copyright infringement? ;

Your opinion is important to us! Was the published material useful? Yes | No

Dividing the sides of the current triangle into U

, we obtain a rectangular triangle of conductivities, similar to
a triangle of voltages (Figure 2.21, a, b
).

If each side of the voltage triangle is multiplied by the same current, you get a similar triangle, the sides of which are proportional to the power.

P - active power, W This is the power that is released in the form of heat or in the form of mechanical energy. Active power is released at the resistance R. Q - reactive power, measured in Var (Voltamper - reactive) This is the power that is released at the inductance. Reactive power does not create any benefit. S is the total power of the circuit, which is equal to the geometric sum of active and reactive powers. Apparent power is the power that the source is forced to deliver to the circuit. The source delivers full power, which is more than useful power due to the inductance of the circuit.

Three-phase electrical circuits. The main advantages of a three-phase electrical circuit. Three-phase EMF and its vector diagram. Obtaining three-phase EMF. Three-phase generator. Unconnected (six-wire) and coupled (four-wire) electrical energy transmission lines.

A three-phase circuit is a set of electrical circuits in which three sinusoidal emfs operate. of the same frequency, different in phase from one another (φ = 120 o) and created by a common energy source.

Main advantages of a three-phase system

: the ability to easily obtain a circular rotating magnetic field (this made it possible to create AC electric motors), economy and efficiency (power can be transmitted through three phase wires without the use of a fourth common wire - neutral), as well as the ability to use two different operating voltages in one installation (phase and linear, which are usually 220 V and 380 V, respectively). Three-phase current is the simplest system of multiphase currents capable of creating a rotating magnetic field. A three-phase circuit consists of a three-phase generator, a three-phase power line and three-phase receivers.

Connection diagrams for triangle and star windings for dummies.

The most common question for those beginning to study the design of transformers or other electrical devices is “What are star and triangle?” We will try to explain in our article how they differ and how they are structured.

Let's consider the winding connection diagrams using the example of a three-phase transformer. In its structure, it has a magnetic circuit consisting of three rods. Each rod has two windings - primary and secondary. High voltage is applied to the primary, and low voltage is removed from the secondary and goes to the consumer. In the symbol, the connection diagram is indicated by a fraction (for example, Y⁄∆ or Y/D or U/D), the numerator value is the connection of the high voltage (HV) winding, and the denominator value is the low voltage (LV).

Each rod has both a primary winding and a secondary winding (three primary and three secondary windings). Each winding has a beginning and an end. The windings can be connected to each other using a star or delta method. For clarity, let us denote the above schematically (Fig. 1)

When connected by a star, the ends of the windings are connected together, and three phases go from the beginning to the consumer. From the terminal connections of the ends of the windings, the neutral wire N (also known as neutral) is removed. The result is a four-wire, three-phase system, which is often found along overhead power lines (Fig. 2)

The advantages of this connection scheme are that we can get 2 types of voltage: phase (phase + neutral) and linear. In such a connection, the linear voltage is √3 times greater than the phase voltage. Knowing that the phase voltage gives us 220V, multiplying it by √3 = 1.73, we get approximately 380V - linear voltage. But as for the electric current, in this case the phase current is equal to the linear one, because Both linear and phase currents leave the winding in the same way, and it has no other path. It is also worth noting that only in the star connection there is a neutral wire, which is a load “equalizer” so that the voltage does not change or jump.

Let us now consider the connection of the windings with a triangle. If we connect the end of phase A to the beginning of phase B, connect the end of phase B to the beginning of phase C, and connect the end of phase C to the beginning of phase A, we will get a triangle winding connection diagram. Those. in this circuit the windings are connected in series. (Fig. 3)

Basically, this connection scheme is used for symmetrical loads, where the load does not change between phases. In such a connection, the phase voltage is equal to the linear voltage, but the electric current, on the contrary, is different in such a circuit. The linear current is √3 times greater than the phase current. The delta connection of the winding provides ampere-turn balance for zero current

sequences. In simple terms, the delta connection circuit provides balanced voltage.

Let's summarize. For a basic definition of power transformer winding connection diagrams, it is necessary to understand that the difference between these connections is that in a star, all three windings are connected together by one end of each winding at one (neutral) point, and in a triangle, the windings are connected in series. The star connection allows us to create two types of voltage: linear (380V) and phase (220V), and in a triangle only 380V.

The choice of winding connection diagram depends on a number of reasons:

  • Transformer power circuits
  • Transformer power
  • Voltage level
  • Load asymmetry
  • Economic considerations

For example, for networks with a voltage of 35 kV and more, it is more profitable to connect the transformer winding with a star circuit, grounding the zero point. In this case, it turns out that the voltage of the transformer terminals and transmission line wires relative to the ground will always be √3 times less than linear, which will lead to a reduction in the cost of insulation.

In practice, the following groups of compounds are most often encountered: Y/Y, D/Y, Y/D.

The group of winding connections Y/Y (star/star) is most often used in low-power transformers that supply symmetrical three-phase electrical appliances/receivers. It is also sometimes used in high-power circuits when grounding of the neutral point is required.

The winding connection group D/Y (delta/star) is used mainly in high-power step-down transformers. Most often, transformers with such a connection operate as part of power supply systems for low-voltage current distribution networks. Typically, the star's neutral point is grounded to accommodate both line-to-line and phase-to-phase voltages.

The Y/D (star/delta) winding connection group is mainly used in the main transformers of large power stations and non-distribution substations.

Source: www.forwardenergo.ru

Power triangle and cos φ

For clarity, let us depict the total power and its components in the form of vectors (see Fig. 2). Let us denote the total power vector by the symbol S, and assign the symbols P and Q to the vectors of the active and reactive components, respectively. Since the vector S is the sum of the current components, then, according to the rule of vector addition, a power triangle is formed.

Applying the Pythagorean theorem, we calculate the modulus of the vector S:

From here you can find the reactive component:

We have already mentioned above that reactive power depends on the phase shift, and therefore on the angle of this shift. It is convenient to express this dependence in terms of cos φ. By definition, cos φ = P/S. This value is called the power factor and is denoted P f. Thus, P f = cos φ = P/S.

Power factor, that is, cos φ, is a very important characteristic that allows you to evaluate the efficiency of current operation. This value is in the range from 0 to 1.

If the phase shift angle takes a zero value, then cos φ = 1, which means that P = S, that is, the total power consists only of active power, and there is no reactance. When the phases are shifted by an angle π/2, cos φ = 0, which means that only reactive currents dominate in the circuit (in practice, this situation does not arise).

Rating
( 1 rating, average 4 out of 5 )
Did you like the article? Share with friends:
For any suggestions regarding the site: [email protected]
Для любых предложений по сайту: [email protected]