Description
The operating principle of electronic AC active energy watt-hour meters "Mercury 201" is based on taking into account information received from the pulse output of the measuring microcircuit. The meters use a shunt connected in series with the current circuit as current sensors. Resistive dividers connected to a parallel voltage circuit are used as voltage sensors.
As a counting mechanism, the meters have electromechanical readout devices (CD) or liquid crystal indicators (LCD) according to Table 1.
Meters with UO provide information display in the form of six-digit numbers, the five highest digits give readings in kWh, the sixth digit indicates the value of electricity in tenths and hundredths of kWh.
Meters with LCDs provide cumulative display of energy consumption in the form of eight-digit numbers, the six highest digits give readings in kWh, the two lowest ones indicate tenths and hundredths of kWh.
The meters have a light indication of power consumption. The flickering period of the indicator light is proportional to the level of energy consumption.
The meters have an electrical or optical pulse output as a test output device.
Meters can be used autonomously or in automated systems for collecting and recording information about consumed electricity.
Electronic watt-hour meters of active energy of alternating current "Mercury 201" consist of the following components:
— housing (case base, housing cover, terminal cover);
— terminal block;
— printed circuit assembly.
The printed circuit assembly is a board with electronic components that is installed at the base of the housing. The printed circuit board is connected to the terminal block using wires.
The housing cover is attached to the base with latches and one or two screws (depending on the modification) and has a window for reading readings from the LCD (LC) and for observing the LED operation indicator.
The terminal block consists of four terminals for connecting the mains and load.
On the printed circuit there are:
- power unit;
— pulse output optocoupler;
— microcontroller (MK);
— non-volatile storage device;
- LCD (UO).
The meters are designed for use indoors.
The degree of protection of meters against penetration of dust and water is IP51.
Electronic watt-hour meters of active energy of alternating current "Mercury 201" have several versions, differing:
— base and maximum current;
— accuracy class;
— counter constant;
— a device for displaying metered electricity;
— the presence of an electrical or optical test output;
— functionality;
— climatic design;
- type of housing.
Options for meter designs are shown in Table 1.
Table 1 - Meter options
Modifications counter | Constant counter, imp./(kWh) | Base (maximum) current, A | Type indicator | Additional functions |
Mercury 201.1 | 6400 | 5(60) | UO | — |
Mercury 201.2 | 6400 | 5(60) | LCD | — |
Mercury 201.22 | 6400 | 5(60) | LCD | PLC |
Mercury 201.3 | 6400 | 10(80) | UO | — |
Mercury 201.4 | 6400 | 10(80) | LCD | — |
Mercury 201.42 | 6400 | 10(80) | LCD | PLC |
Mercury 201.5 | 3200 | 5(60) | UO | — |
Mercury 201.6 | 3200 | 10(80) | UO | — |
Mercury 201.7 | 3200 | 5(60) | UO | — |
Mercury 201.8 | 5000 | 5(80) | LCD | — |
Mercury 201.82 | 5000 | 5(80) | LCD | PLC |
Mercury 201.9 | 3200 | 10(80) | UO | — |
UO - electromechanical readout device,
LCD - liquid crystal indicator,
PLC is a modem module for transmitting information over a power network.
A general view of electronic AC active energy watt-hour meters "Mercury 201", manufactured in different housings, is presented in Figures 1 - 4.
The sealing diagram against unauthorized access and the designation of the place where the verification mark is applied are presented in Figures 5, 6.
Figure 4
The verification mark is applied by pressure to a hinged seal or special mastic.
Design features and connection diagram
The device consists of a plastic case, a cover, a terminal block, an optocoupler, a volatile memory device, an optoport, a microprocessor and a liquid crystal monitor. There are two connection options. Can be connected directly or semi-indirectly using current three-phase transformer installations. As for direct connection, the device is connected directly to the power line according to the instructions using input machines.
You may be interested in this Procedure for replacing an electric meter
Note! As for semi-indirect connection and installation, this circuit uses a phase network conductor. It is worth pointing out that there is also an autotransformer, indicated in the diagram.
Mercury connection 201
Specifications
Table 3 - Metrological characteristics
Characteristic name | Meaning |
Accuracy class | 1 or 2 according to GOST 31819.21-2012 |
Rated voltage, V | 230 |
Set operating voltage range | from 0.9 to 1.Shnom |
Extended operating voltage range | from 0.8 to 1.15in |
Limit operating voltage range | from 0 to 1.15in |
Base current (1b), A | 5 or 10 |
Maximum current (1max), A | 60 or 80 |
Rated network frequency, Hz | 50 |
Starting current (sensitivity), mA, no more: - for a meter with 3^=5 A | 20 |
- for a meter with 1b=10 A | 40 |
Meter constant, imp./kWh | 6400 or 5000 or 3200 |
Liquid crystal indicator: - number of displayed digits | 8 |
— unit price of the least significant digit when displaying energy, kWh | 0,01 |
Reading device: — number of displayed digits | 6 |
— unit price of the least significant digit when displaying energy, kWh | 0,01 |
Number of tariffs | 1 |
Table 4 - Main technical characteristics
Characteristic name | Meaning |
Total power consumed by the current circuit, VA, no more | 0,1 |
Active power consumed by the voltage circuit, W, no more than: - for counters — for meters with PLC modem | 2 3,5 |
Total power consumed by the voltage circuit, VA, no more than: - for counters — for meters with PLC modem | 10 25 |
Overall dimensions of the meter, mm, no more: - height - width - length | 105 or 91* 105 or 77* 64 or 66* |
Weight, kg, no more | 0,34 |
Established operating temperature range, °C | -40 to +55 (-45 to +75)* |
Average meter service life, years | 30 |
Average time between failures of the meter, h | 220000 |
* for meters “Mercury 201.7”, “Mercury 201.8”, “Mercury 201.82”, “Mercury 201.9” |
Counter MERCURY 201.8 TLO
BUY METER MERCURY 201.8TLO
You can view the prices and buy a single-phase electric meter MERCURY 201.8 TLO at wholesale prices on our website. Wide range of equipment and options, delivery to any point in the Russian Federation and CU countries. Official warranty, supply of spare parts, post-warranty service. We will offer the best price for electric meters. You can also send a request for selection of an electric meter using the form below.
TO ORDER PRODUCTS CONTACT US IN A WAY CONVENIENT FOR YOU:
Tel | Email | Feedback form
CATALOG OF MERCURY COUNTERS
FEATURES OF THE ELECTRICITY METER MERCURY 201.8 TLO
Measurement, accounting, storage, output to LCD and transmission via interfaces of active and reactive electricity separately for each tariff and the amount for all tariffs for the following periods of time:
- energy from resetting the readings;
- energy at the beginning of the current and 180 previous days;
- energy at the beginning of the current and 48 previous months.
Tariff with the ability to set a separate schedule for each day of the week at 4 tariffs in 16 time zones of the day. Each month of the year is programmed with an individual tariff schedule. Measuring electrical network parameters:
- instantaneous values of active, reactive and apparent power;
- effective values of current and voltage;
- network frequency;
- Power factor.
Power profile with averaging time of 30 minutes and storage depth of 6 months.
Recording maximum current, voltage, active and reactive power. Maintaining event logs. Automatic self-diagnosis with error indication. Availability of a built-in 80 A relay. Non-volatile electronic seal. Recording unauthorized actions in permanent event logs. Indication of parameters on the LCD when the power is off. Absence of magnetically sensitive elements in the measuring circuits and power supply system. Compact housing with DIN rail mounting.
The counters are displayed on the LCD indicator:
- current tariff number (TARIFF 1…4) and amount;
- the value of consumed energy of each type from the beginning of operation for each tariff and the amount for all tariffs;
- current value of active and reactive power in the load and their maximums;
- current current and voltage values and their maximums;
- power and energy limit;
- exceeding the power limit;
- the value of energy consumed from the beginning of operation on the first day of the current month and each of the previous 11 months for each tariff and the amount for all tariffs;
- time of switching tariff zones for the current day;
- time and date;
- operating time from the moment the meter was put into operation;
- battery operating time;
- indicator of disconnected relay;
- reverse current indicator.
METROLOGICAL CHARACTERISTICS OF MERCURY 201.8 TLO
Meter accuracy class (active / reactive): | 1/2 |
Rated voltage, V: | 230 |
Base / maximum current, A: | 5/80 |
Maximum current for 10ms: | 30*I max |
Sensitivity when measuring active energy, A: | 0,02 |
TECHNICAL SPECIFICATIONS MERCURY 201.8 TLO
Active / total power consumption by the meter voltage circuit at rated voltage, W/V*A | 2 / 10 |
Total power consumed by each current circuit, no more, V*A | 0,1 |
Additional active / apparent power consumption of the meter voltage circuit at rated voltage for the PLC interface, W/V*A | 2 / 12 |
Number of tariffs | 4 |
Data safety during power interruptions, at least years | 10 |
Calibration interval, years | 16 |
Warranty period, years | 3 |
MTBF, no less, h | 220 000 |
Operating temperature range, °C | from -45 to +75 |
Weight, no more, kg | 0,6 |
Dimensions (LxWxH), mm | 128x90x65 |
LEGEND MERCURY 201.8 TLO
T – internal tariff, electronic seals; L – PLC-II modem; О – built-in power relay for load control.
DIMENSIONAL DRAWING OF THE METER MERCURY 201.8 TLO
Completeness
Table 5 — Completeness of meters
Name | Designation | Quantity |
Electronic AC active energy watt-hour meter “Mercury 201.1” (or “Mercury 201.2”, “Mercury 201.22”, “Mercury 201.3”, “Mercury 201.4”, “Mercury 201.42”, “Mercury 201.5”, “Mercury 201.6”, "Mercury 201.7", "Mercury 201.8", "Mercury 201.82", "Mercury 201.9") in consumer packaging | AVLG 537.00.00 | 1 PC. |
Passport | AVLG.411152.023PS | 1 copy |
Technological device RS-232 - PLC | AVLG.468152.018* | 1 PC. |
Test software ":BMonitor" on magnetic media* | — | 1 PC. |
Medium Repair Guide | AVLG.411152.023RS** | 1 PC. |
* Supplied upon separate order to organizations that verify and operate meters. ** Delivered upon separate order to organizations conducting post-warranty repairs. |
Verification
carried out in accordance with GOST 8.584-2004 “Static active electrical energy meters of alternating current. Verification methodology."
Basic means of verification:
Working standard of the 2nd category according to GOST 8.551-2013, installation for checking electric energy meters automated UAPS-1M, registration number in the Federal Information Fund No. 23832-07 (rated voltage 230 V, main operating current range (0.01-100) A, active energy measurement error ±0.15%).
It is allowed to use similar verification tools that ensure the determination of the metrological characteristics of the meters being verified with the required accuracy.
The verification mark is applied by pressure to a special mastic or hinged seal, which is located at the point where the casing is attached to the base of the meter.
Basic and additional characteristics
There are differences in the technical characteristics of the device depending on the model, but the common feature for meters of the 201 series is accuracy class 1. This meets the requirements of regulatory documents (no more than 2) and indicates a small measurement error. The device is protected by a polarity reversal system from the possibility of external influence on its operation. You cannot stop the device or affect the accuracy of the data.
- rated network voltage - 230 V;
- rated current - 5(60) - 10(80) A;
- sensitivity threshold - 10/20/40 mA;
- temperature range within -40…+75⁰С;
- weight - 0.25 (0.35) kg.
- service life - 30 years;
- The warranty period is 3 years.